Table 6.2 - Allowance for diversity
|
|||
Note the following abbreviations : |
|||
Type of final circuit |
Type of premises |
||
Households |
Small shops, stores, offices |
Hotels, guest houses |
|
Lighting |
66% total demand |
90% total demand |
75% total demand |
Heating and power | 100% up to 10 A + 50% balance |
100%X + 75%(Y+Z) |
100%X + 80%Y + 60%Z |
Cookers |
10 A + 30% balance + 5 A for socket |
100%X + 80%Y + 60%Z |
100%X + 80%Y + 60%Z |
Motors (but not lifts) |
100%X + 80%Y + 60%Z |
100%X + 50%(Y+Z) |
|
Instantaneous water heaters | 100%X + 100%Y + 25%Z |
100%X + 100%Y + 25%Z |
100%X + 100%Y + 25%Z |
Thermostatic water heaters |
100% |
100% |
100% |
Floor warming installations |
100% |
100% |
100% |
Thermal storage heating | 100% |
100% |
100% |
Standard circuits | 100%X + 40%(Y+Z) |
100%X + 50%(Y+Z) |
100%X + 50%(Y+Z) |
Sockets and stationary equip. |
100%X + 40%(Y+Z) |
100%X + 75%(Y+Z) |
100%X + 75%Y + 40%Z |
Extracted from The Electricians Guide Fifth Edition
by John Whitfield
Published by EPA Press Click Here to order your Copy.