Table 8.4 - Suggested intervals
between
------------- periodic tests and inspections |
|
Type of installation |
Maximum period between
inspections |
Domestic premises |
10 years |
Commercial premises |
5 years |
Educational establishments |
5 years |
Hospitals |
5 years |
Industrial premises |
3 years |
Cinemas |
1 year* |
Churches |
5 years |
Leisure complexes |
1 year |
Places of public entertainment |
1 year |
Theatres, etc. |
1 year* |
Agricultural and horticultural |
3 years |
Caravans |
3 years |
Caravan sites |
1 year* |
Emergency lighting |
3 years |
Fire alarm systems |
1 year |
Launderettes |
1 year* |
Petrol filling stations |
1 year* |
Public Houses |
5 years |
Marinas |
1 Year |
Highway power supplies |
6 years |
Temporary installation |
3 months |
Where maximum periods are marked
*
there is a legal requirement for retests at these intervals |
Extracted from The Electricians Guide Fifth Edition
by John Whitfield