This pipe freeze protection cable is comprised of a heating cable, thermostat and power cord and may only be used for freeze protection of metal or plastic water pipes up to 40 mm diameter. Read carefully and follow these instructions for an efficient, economical and safe installation. We recommend you retain these instructions for future reference.
Before applying the heating cable, ensure that the area on and around the pipe is free and clear of sharp edges and combustible materials (to minimize the risk of damage to the cable and adjacent areas).
If you are applying the heating cable to a plastic pipe, we recommend that you first wrap the pipe with aluminum foil before applying the heating cable. The aluminum foil distributes the heat from the heating cable uniformly around the pipe, as aluminum is a better heat conductor than plastic.
For UK installations the two pin plug should be removed. Connection to the mains should be made in accordance with current regulations and by a qualified person. The cable must be earthed.
The thermostat (the black cap in the orange block) must be placed tightly against the pipe and secured with PVC electrical tape. Do not use any type of strapping. The thermostat should be placed on the coldest end of the pipe. The thermostat will sense the temperature of the pipe and turn the cable on and off as required to prevent the pipe from freezing and to provide economical operation.
Using a good quality PVC electrical tape, lay the heating cable on the pipe and fasten it to the pipe at approximately 600 mm intervals.
For pipe freeze protection under extremely cold conditions, or for minimizing energy consump-tion, it is recommended that insulation be added to the pipe over the heating cable. The heating cable/ pipe may be insulated with either fibreglass or polyethylene foam insulation.
INSULATION MUST BE APPLIED TO THE THERMOSTAT IN THE SAME MANNER AS THE REST OF THE HEATING CABLE/PIPE to ensure that all sections of the pipe are maintained at the same temperature. If the thermostat area is insulated moreso than the rest of the pipe, then the rest of the pipe will not be kept as warm as the thermostat area and may freeze. If the thermostat area is not insulated as well as other areas of the pipe, the thermostat will be turning the cable on for longer periods than necessary, resulting in uneconomical operation. (The thermostat turns the heating cable on when it senses temperatures of approximately 3°C or less, and turns the heating cable off when it senses temperatures of approximately 13°C or more).
FOR MINERAL WOOL INSULATION, A MAXIMUM OF 13 mm of insulation may be applied over the heating cable. It is important to note that mineral wool insulation can be damaged by moisture, hence a waterproof overwrap must be applied to the insulation to prevent moisture penetration. FOR FOAMED INSULATION, A MAXIMUM OF 13 mm of insulation may be applied over the heating cable. Foamed insulation is usually not affected by moisture, hence waterproofing is usually not required.
Once the cold/winter season begins, plug the power cord into an appropriate receptacle. (See also “Operation” below)
1) Lightly cut around heater overjacket 127mm from the end. Bend cable to break the overjacket.
2) Lightly cut overjacket up the center between first cut mark and the cable end. Bend cable to break the overjacket.
3) Remove overjacket from heater cable.
4) Move braid back toward the overjacket, creating a bulge.
5) At the bulge, separate the braid to make an opening.
6) While bending the heater cable, work it through the braid opening.
7) Pull the braid tight.
8) Lightly cut around heater outer jacket 48mm from the end. Bend cable to break outer jacket.
9) Lightly cut the outer jacket up the center between the first cut mark & the cable end. Bend cable to break outer jacket.
10) Remove the jacket from the heater cable.
11) Shave the core material from the outside of each bus wire.
12) Starting at the end, pull each bus wire away from the core material.
13) Remove exposed core material.
14) Slide one 3mm diameter, 25mm length shrink tube over each bus wire, leaving approximately 13mm of each bus wire exposed. Shrink with heat gun until completely shrunk.
15) Slide a 13mm diameter, 51mm length shrink tube over both pigtail leads leaving approx. 25mm of each pigtail lead exposed. Shrink with heat gun until completely shrunk.
16) While still warm, spread bus wires and squeeze between them using needle-nose pliers, hold for 5 seconds.
1) Strip overjacket and braid back 102mm from the end. Slide braid back over the overjacket portion of the heater cable.
2) Cut off excess heater cable leaving 25mm.
3) At the end of the heater cable, snip a 10mm slit between the bus wires. Slightly spread wires apart.
4) Slide a 13mm diameter, 51mm length shrink tube over the heater cable leaving approximately 25mm of shrink tube past the heater cable. Shrink with heat gun until completely shrunk.
5) While still warm, squeeze the entire width of shrink tube closed. Cut off excess shrink tube.
6) Pull braid over the squeezed shrink tube, covering the entire end seal and twist closed.
7) Fold twisted braid back and slide the 16mm diameter, 76mm length shrink tube over the braid leaving 13mm of shrink tube past the braid. Shrink with heat gun until completely shrunk.
8) While still warm, squeeze shrink tube closed. Make sure to seal the entire width of tubing.
Use table 1 to select the correct product. In most instances the cable can be applied in a straight line along the length of the pipe but if an even spiralling is required, this is indicated. The table is based on pipe freeze protection against -20°C.
Table1
Pipe Diam (mm) | Insulation Thickness | ||
---|---|---|---|
12mm | 25mm | 50mm | |
12 | CCSR-10 Straight |
CCSR-10 Straight |
CCSR-10 Straight |
25 | CCSR-15 Straight |
CCSR-10 Straight |
CCSR-10 Straight |
50 | CCSR-24 Straight |
CCSR-10 Straight |
CCSR-10 Straight |
75 | CCSR-24 1.3m cable/1m pipe |
CCSR-24 Straight |
CCSR-10 Straight |
100 | CCSR-24 1.8m cable/1m pipe |
CCSR-24 Straight |
CCSR-15 Straight |
150 | CCSR-24 3m cable/1m pipe |
CCSR-24 1.4m cable/1m pipe |
CCSR-15 1.2m cable/1m pipe |
Table 2 -
Additional length for flanges, valves and supports (m)
Pipe Diam. (mm) | Pair of Flanges | Valve | Support |
12 | 0.23 | 0.10 | 0.10 |
25 | 0.28 | 0.15 | 0.10 |
50 | 0.30 | 0.30 | 0.15 |
75 | 0.45 | 0.40 | 0.15 |
100 | 0.60 | 0.50 | 0.20 |
150 | 0.80 | 0.60 | 0.25 |
Example: To frost protect a 75mm diameter pipe 10 metres long. To be fully insulated with 25mm thick insulation. The pipe has 10 supports and the lowest temperature is –20ºC.
1) From the Table 1 cross reference 75mm diameter and 25mm insulation. Select CCSR-24 installed straight along the pipe.
2) Length of cable required is 10m (as cable to be installed straight along the pipe).
3) Add extra length for the support (Table 2) 10 x 0.15 = 1.5m.
4) Total length of cable = 10 + 1.5 = 11.5m of CCSR-24 + 1 CCSR-T 1 termination kit.
Ref No | Maximum Output W/M@10°C |
Length | Voltage | Maximum Exposure Temperature (Intermittent) | Minimum Installation Temperature | Maximum Circuit Length |
---|---|---|---|---|---|---|
CCSR-10 -CL | 10 | By the metre | 230 | 66 °C | -20 °C | 164m |
CCSR-10 | 10 | 75m dispensing box | 230 | 66 °C | -20 °C | 164m |
CCSR-15-CL | 15 | By the metre | 230 | 66 °C | -20 °C | 140m |
CCSR-15 | 15 | 75m dispensing box | 230 | 66 °C | -20 °C | 140m |
CCSR-24-CL | 24 | By the metre | 230 | 66 °C | -20 °C | 106m |
CCSR-24 | 24 | 75m dispensing box | 230 | 66 °C | -20 °C | 106m |
Termination and splice/tee kits available.
For overriding control, internal and external mounting air thermostats available (FST-IN and FST-EX).