Features
Benefits
One 12v battery as back up The Mag4 only needs 1 x 12v battery as back up supply. The Mag4 has a built in transformer which converts 12v from the battery to 24v.
Unlimited number of call-points Unlimited number of call-points can be connected to each zone on the Mag4.
30 fire detectors per zone Up to 30 fire detectors can be connected to each zone on a Mag4. Therefore the Mag4 is able to power a maximum of 60 detectors.
Individual zone fault identification If there is a fault on a zone the panel is able to indicate which zone has a problem via lighting up the fault LED alongside the zone. This is situated on the front LED display board.
Sounder circuit fault identification If there is a fault on a sounder circuit the panel is able to indicate which sounder circuit has a problem via lighting up the fault LED alongside the sounder circuit. This is situated on the front LED display board.
Fault identification To help the end user or installer to determine the cause of the fault there are fault indication LED's located on the front LED display board. These LED's are marked as low battery, battery loss, no AC, earth, processor, zone power etc.
Individual zone isolate The Mag4 can be programmed so that individual zones can be isolated (disabled) which allows an engineer/installer carry out maintenance work without the worry that the panel will go into fault condition.
One man test facility The one man test facility enables an engineer/installer to test all detection devices connected to a zone one by one. The panel indicates its status via a series of bleeps plus the sounders come on for one second to confirm activation.
Class change facility The class change facility is an input, which can be used to activate the sounders/bells connected to the panel via an external device. Class change facility would be used in places such as schools.
Fire relay Device(s) which need to be activated when the panel is in fire condition can be connected to the fire relay i.e. magnetic door holders.

Fault relay Device(s) which need to be activated when the panel is in fault condition can be connected to the fault relay i.e. fault indication light etc.
Plug in terminal blocks For ease of installation the connection terminal blocks can be removed and placed back on the PCB as desired.

Max number of zones: 4
Main power supply: 230V AC +- 10%
Standby power supply: 1 x 12V (12V) Sealed lead acid batteries
Max current available: 0.7A
Current consumption - mains failure: 50mA
Sounder circuit 1: 24V / 0.315A - 0.3A fuse
Sounder circuit 2: 24V / 0.315A - 0.3A fuse
Auxiliary output:: 24V DC - 0.3A fuse
Cabling: Maximum 2.5mm diameter
Dimensions:

220(w) x 320(h) x 80(d) mm
Working temperature: 0 to 40ºC
Storage temperature: -20 to 60ºC

Humidity:

0 to 95%

 