Standard Features:
PCS100 |
|
|
* Fully Monitored Sensor and Sounder
--Circuits to BS 5839 Part
4 1988. |
|
* Twin Sounder Circuit Outputs. |
* Surface Mounting complete with
--hinged lid. |
|
* Open and Short Circuit provides fault
--indication. |
* Complete with integral charger for
--Sealed Lead Acid Batteries. |
|
* Class Change/Remote Evacuate input. |
|
|
* Dimensions: 305mm x 205mm
x 100mm |
|
|
|
Standard Features:
PCS100HR |
|
|
* Fully Monitored Sensor and Sounder
--Circuits to BS 5839 Part
1 1988. |
|
* Twin Sounder Circuit Outputs. |
* Complete with Detector Removal Alarm
--Circuit without affecting
the normal operation
--of any manual call point. |
|
* Open, Short Circuit and Head Removal on
--sensor loop provides Indication. |
* Surface Mounting complete with hinged
lid. |
|
* Class Change/Remote Evacuate input. |
* Complete with integral charger for Sealed
--Lead Acid Batteries. |
|
* Dimensions: 305mm x 205mm x 100mm. |
CONTROLS |
|
|
Rotary Keyswitch to carry out the
following functions: |
* Reset |
|
* Evacuate |
* Alarm Silence |
|
* Lamp Test |
INDICATORS |
|
|
* Mains On |
|
* Sounder Fault |
* Fire |
|
* Power Supply Fault |
* Sensor Fault |
|
|
OUTPUTS |
|
|
* Two Sounder Circuits each rated
at 250mA at 24vDC |
PANEL
SPECIFICATION |
PCS100
|
PCS100HR
|
Quiescent Current Drain in
Mains/Charger Fail Condition |
55mA
|
70mA
|
Standby Time of System
with 2.6AH Batteries |
36 Hours
|
30 Hours
|
Standby Time of System with 6.0AH
Batteries |
88 Hours
|
76 Hours
|
Weight (without batteries) |
4 Kgs
|
4 Kgs
|
|
|
|
SENSOR MONITORING
|
|
|
Open and Short Circuit Fault |
Yes
|
Yes
|
Head Removal to BS 5839 Part 1 |
No
|
Yes
|
ALL PANELS |
|
* Mains Supply Voltage |
- 220/250v AC 50/60HZ |
* Internal Power Supply |
- 24v DC Nominal |
* Total Output Current Limited To |
- 1A @ 24vDC |
* Battery Requirement |
- 2 x 12v Sealed Lead Acid Baterries
--Space available for
6AH capacity |
* Monitoring - Sounder Circuits |
- Open and Short Circuit
--Control Board - Mains
and Charger Failure,
--Battery Disconnection |
* Max. No. of Detectors per zone |
- 20 |
* Max. No. of Break Glass per zone
|
- No Limit |
* Sounder Outputs fused at |
- 250mA |
* Max. No. of Bells @ 25mA each |
- 10 per Sounder circuit - Total 20 |
* Max. No. of Electronic Sounders
@ 20mA each |
- 12 per Sounder circuit - Total 24 |
* Maximum Total Sounder Load on the
panel is 500mA |
|
* Class Change Remote
Evacuate Input |
- Included in all Panels |
* Link select for Sensor
Short Circuit = Fire |
- Included in all Panels |
OPTIONAL EXTRAS |
FARM |
- PCB complete with 2 sets of volt
Free Relay Changeover Contacts which
--operate on any zone
in fire.
--These contacts are
rated at 3A 250vAC resistive load. |
FIREFAULT |
- PCB complete with two relays, one
for common fire conditions with LED
--indication, one for
common fault conditions with LED indication. Each
relay is
--rated at 24vDC 1A.
|
NOTE Only one of the Farm
or Firefault may be fitted to each panel.
|
|