TWO AND FOUR ZONE FIRE ALARM SYSTEMS

 

Standard Features: PCS200 and PCS400
* Fully Monitored Sensor and Sounder
--Circuits to BS 5839 1988.
* Twin Sounder Circuit Outputs.
* Surface Mounting complete with
--hinged lid.
* Open and Short Circuit provides fault
--indication.
* Complete with integral charger for
--Sealed Lead Acid Batteries.
* Fire output per zone for Repeater Panels.
  * Dimensions: 305mm x 205mm x 100mm

HEAD REMOVAL ADDITIONAL FEATURE FOR ABOVE PANELS
* Addition of HRMODULE provides head
--removal facility to simplify compliance to
--BS 5839 Part 1 1988. Sec 6.6.2 AMD 6317
--1991.
* HRMODULE provides Detector
--Removal Alarm Circuit without
--affecting the normal operation of
--any manual call point.
* Open, Short Circuit and Head Removal on
--sensor loop provides fault indication.
 

CONTROLS - Keyswitch to ENABLE the operation of:

* Reset Push Button * Evacuate Switch
* Alarm Silence Push Button * Lamp Test

INDICATORS  
* Mains On * Sounder Fault
* Common Fire * Power Supply Fault
* Common Fault * Alarm Silenced
* Zone Fire * Evacuate Operated
* Zone Fault  

OUTPUTS
* Two Sounder Circuits each rated at 250mA at 24vDC
* Fire Output per zone and Common Fault to operate Repeater panels with a 4 core cable for
--PCS200 and a 6 core cable for PCS400.

PANEL SPECIFICATION
PCS200
2 ZONE
PCS400
4 ZONE
Quiescent Current Drain in
Mains/Charger Fail Condition
60mA
70mA
Standby Time of System with 2.6AH Batteries
36 Hours
30 Hours
Standby Time of System with 6.0AH Batteries
88 Hours
76 Hours
Weight (without batteries)
4 Kgs
4 Kgs
     
SENSOR MONITORING
Open and Short Circuit Fault
   
Head Removal to BS 5839 Part 1
Yes
Yes
When HRMODULE fitted
Yes
Yes

ALL PANELS  
* Mains Supply Voltage - 220/250v AC 50/60HZ
* Internal Power Supply - 24v DC Nominal
* Total Output Current Limited To - 1A @ 24vDC
* Battery Requirement - 2 x 12v Sealed Lead Acid Baterries
--Space available for 6AH capacity
* Monitoring - Sounder Circuits - Open and Short Circuit
--Control Board - Mains and Charger Failure,
--Battery Disconnection
* Max. No. of Detectors per zone - 20
* Max. No. of Break Glass per zone - No Limit
* Sounder Outputs fused at - 250mA
* Max. No. of Bells @ 25mA each - 10 per Sounder circuit - Total 20
* Max. No. of Electronic Sounders @ 20mA each - 12 per Sounder circuit - Total 24
* Maximum Total Sounder Load on the panel is 500mA  
* Class Change Remote Evacuate Input - Included in all Panels

OPTIONAL EXTRAS
HRMODULE - PCB to be fitted at the end of each zone to give head removal operation facility.
FARM - PCB complete with 2 sets of volt Free Relay Changeover Contacts which --operate on any zone in fire.
--These contacts are rated at 3A 250vAC resistive load.
FIREFAULT - PCB complete with two relays, one for common fire conditions with LED --indication, one for common fault conditions with LED indication. Each relay is --rated at 24vDC 1A.
NOTE Only one of the Farm or Firefault may be fitted to each panel.

PCSR4Z - 2/4 Zone Repeater panel, fire LED,s per zone and a common fault LED. --Dimensions 136mm x 196mm.
PCS24RTPCB
- Termination board for control panel to enable connection of wiring to repeater --panel PCSR4Z