* Addition of HRMODULE provides head
--removal facility to simplify
compliance to
--BS 5839 Part 1 1988. Sec
6.6.2 AMD 6317
--1991. |
* HRMODULE provides Detector
--Removal Alarm Circuit without
--affecting the normal operation
of
--any manual call point. |
* Open, Short Circuit and Head Removal on
--sensor loop provides fault
indication. |
|
CONTROLS - Keyswitch to ENABLE the operation
of:
|
* Reset Push Button |
* Evacuate Switch |
* Alarm Silence Push Button |
* Lamp Test |
OUTPUTS |
* Two Sounder Circuits each rated at 250mA at 24vDC |
* Fire Output per zone and Common Fault to operate Repeater
panels with a 4 core cable for
--PCS200 and a 6 core cable
for PCS400. |
PANEL SPECIFICATION
|
PCS200
2 ZONE
|
PCS400
4 ZONE
|
Quiescent Current Drain in
Mains/Charger Fail Condition |
60mA
|
70mA
|
Standby Time of System with
2.6AH Batteries |
36 Hours
|
30 Hours
|
Standby Time of System with 6.0AH Batteries |
88 Hours
|
76 Hours
|
Weight (without batteries) |
4 Kgs
|
4 Kgs
|
|
|
|
SENSOR MONITORING
Open and Short Circuit Fault |
|
|
Head Removal to BS 5839 Part 1 |
Yes
|
Yes
|
When HRMODULE fitted |
Yes
|
Yes
|
ALL PANELS |
|
* Mains Supply Voltage |
- 220/250v AC 50/60HZ |
* Internal Power Supply |
- 24v DC Nominal |
* Total Output Current Limited To |
- 1A @ 24vDC |
* Battery Requirement |
- 2 x 12v Sealed Lead Acid Baterries
--Space available for 6AH
capacity |
* Monitoring - Sounder Circuits |
- Open and Short Circuit
--Control Board - Mains and
Charger Failure,
--Battery Disconnection |
* Max. No. of Detectors per zone |
- 20 |
* Max. No. of Break Glass per zone |
- No Limit |
* Sounder Outputs fused at |
- 250mA |
* Max. No. of Bells @ 25mA each |
- 10 per Sounder circuit - Total 20 |
* Max. No. of Electronic Sounders @ 20mA
each |
- 12 per Sounder circuit - Total 24 |
* Maximum Total Sounder Load on the panel
is 500mA |
|
* Class Change Remote Evacuate
Input |
- Included in all Panels |
OPTIONAL EXTRAS |
HRMODULE |
- PCB to be fitted at the end
of each zone to give head removal operation facility. |
FARM |
- PCB complete with 2 sets of volt Free
Relay Changeover Contacts which --operate
on any zone in fire.
--These contacts are rated
at 3A 250vAC resistive load. |
FIREFAULT |
- PCB complete with two relays, one for
common fire conditions with LED --indication,
one for common fault conditions with LED indication. Each
relay is --rated at 24vDC
1A.
|
NOTE Only one of the Farm or Firefault
may be fitted to each panel.
|
PCSR4Z |
- 2/4 Zone Repeater panel, fire LED,s per
zone and a common fault LED. --Dimensions
136mm x 196mm. |
PCS24RTPCB
|
- Termination board for control
panel to enable connection of wiring to repeater --panel
PCSR4Z |