Life
or Property |
BS5839 Part 1, classifies systems and divides
them into six different types: |
L1 |
Intended for life safety and covering the
whole building |
L2 |
Intended for life safety and covering escape
routes and other areas of high risk |
L3 |
Protecting only the escape routes |
P1 |
Intended for property protection and covering
the entire building |
P2 |
Intended for property protection covering
any potentially high risk areas |
M |
Intended for giving the alarm in response
to operation of a manual call point and having no means
of automatic detection |
System
Design |
Before staring the design you will need
to ensure that certain information is available. This
may be given in the specification or it may have to be
obtained by consultation. As well as the purchaser, there
may be a requirement to consult with other interested
parties. The most important of which will probably be
the Fire Prevention Officer of the local Fire Brigade. |
The information which should be available
includes: |
A |
The type of system required ie: L1, L2,
L3 etc and where appropriate, parts of the premises to
be covered. |
B |
The action to be taken in the event of fire |
C |
Whether other occupants of a multi occupancy
building will be affected |
D |
Whether other work is to be done at the
same time. If so then consultation with other contractors
may be required. |
E |
A Method of calling the Fire Brigade |
F |
Whether the type of occupants or activity
in the building will require a greater provision of Manual
Call Points than normal |
G |
A likely attendance time of the Fire Brigade |
Coverage
L1 Systems |
In an L1 System, all areas of the building
should be covered. It is normal not to cover the following
areas: |
|
Lavatories and Water Closets unless they
contain electric hand dryers |
|
Voids less than 800mm in height
|
Coverage
L2 Systems |
Coverage of L2 systems depends on the vulnerability
of the likely occupants and the probability of ignition
of fires, ie: |
|
Sleeping Areas without supervision |
|
Areas having
a high probability of ignition ie: day accommodation,
store rooms, kitchens and plant rooms
|
|
Where occupants are especially vulnerable
due to illness, age or are unfamiliar with the
building. It should be noted that L2 systems always
include L3 coverage.
|
Coverage
L3 Systems |
In L3 systems, coverage should be provided
for escape routes and any areas in which the occurrence
of a fire would directly threaten escape routes. The following
areas should therefore be covered: |
|
Corridors, passages and circulation areas |
|
Stairwells |
|
The top of vertical risers |
|
At
each level within 1.5m of an access point to a lift shaft
or other vertical riser |
|
In all rooms opening onto an escape route |
Coverage
P1 Systems |
In a P1 system all areas of the building
should be covered with the exception of: |
|
Lavatories
and Water Closets |
|
Voids
less than 800mm in height and such that extensive spread
of fire or fire products cannot take place in them prior
to detection by detectors outside the void |
Coverage
P2 Systems
P2 systems give coverage
of only part of the building. The areas covered would
normally have a high fire risk and unprotected areas
should be separated by fire resisting construction.
Both P1 and P2 systems would
invariably be connected to the Fire Brigade via a central
station. It would be on an extremely irregular basis
that you would ever be requested to fit a P type of
system.
|
Manual
only Systems
An A M@ system provides for Manual only alarm and systems intended
for multi occupancy buildings are given the suffix A X @.
|
The
Survey |
If you are surveying a building we would
suggest you start at the top of the building and work
down. Two basic reasons for this are as follows: |
A |
If you are as athletic as the writer of
this guide then you can ride the elevator to the top floor
and the rest of the survey is downhill! |
B |
If you start at the top of the building
then you can be sure to check the top of each stairwell.
This will need a detector (except a Manual only System)
even on an L3 System. As you work your way down the building
you can then check how often detectors are required vertically
down the stairwell. On Type L Systems, BS5839 states
that this shall be at vertical intervals not exceeding
10.5 metres which normally works out to be every third
floor. On Type P Systems, there should be detectors on
every main landing. |
The
Design |
If you are designing onto a set of drawings
then we would recommend that you adopt the following procedure. |
1 |
Identify and plan out where all break glass
points are required. |
2 |
Note where all the Sounders are required.
Indicate where the Control Panel will be. You now have
an > M=System. |
3 |
Consider fitting door holders/closers
onto doors which might otherwise get propped open. Doors
leading onto stairwells should not be fitted with Door
Holders. There was an old GLC regulation which requires
a Smoke Detector to be fitted within 2m either side of
the door or pair of doors fitted with a Door Holder/s
- Closer/s and many authorities ie: West Sussex still
require this. |
4 |
Mark down where all detectors are required
in escape routes, top of stairs, landings, ceilings at
vertical intervals not exceeding 10.5m, top of vertical
risers, within 1.5m of access to lift shafts and within
rooms opening onto escape routes. |
5 |
You should now effectively have the design
of an L3 System and can now go on to add detectors to
bring the system up to L2 or L1 as required. |
6 |
Indicate the number of Zones that will
be required. |
Siting
of Manual Call Points
A Break Glass Call Point
is a device which enables personnel to raise the alarm
by breaking the frangible element on the facia. They
should be mounted 1.4m from the floor and sited where
they can be easily seen.
Manual Call Points should
be sited on the floor landings [4] of stairways and at exits to open air. It should
be noted that many Fire Officers prefer Call Points
to be fitted on the floor side of an access door to
a staircase so the floor of origin is indicated at the
Control Panel. Where necessary, extra points should
be sited [5] so that the greatest travel distance
from any point in the building to the nearest call point
does not exceed 30m. A greater number of Call Points
may be needed in high risk areas or if the occupants
are likely to be slow in movement.
|
Siting
of Sounders
An Alarm Sounder may be
a bell or electronic sounder and it must be audible
throughout the building.
A minimum sound level of
either 65db(A) or 5db(A) above any background noise
likely to persist for longer than 30 seconds, which
ever is the greater, should be produced by the sounders
at any point in the building. It is unlikely that more
than 65DB will be available if the sound has to carry
through more than one door.
If the alarm system is used
in premises such as hotels, boarding houses etc where
the alarm is intended to wake sleeping persons then
the sound level at the bedhead should be at least 75db(A)
with all doors closed. We would strongly recommend
that you allow one sounder per bedroom. A few bells
sprinkled down the corridor in hotel will not produce
75db(A) at all the bedheads.
It is important to note
that the above audibility levels must be produced with
all doors shut, after the works on site have been completed.
If a Fire Officer even expects that there is a lack
of audible sounders, then he is sure to check each area
with a db metre and prove it. It can be costly and
very inconvenient to have to return to site and fit
additional sounders.
A minimum of two sounder
circuits should be wired and a larger number of quieter
sounders are preferable to a small number of very loud
sounders.
At least one sounder should
be installed in each fire compartment and all sounders
throughout an installation must produce a similar sound,
ie: you cannot mix an electronic sounder and bells.
|
Choice
of Detectors
Smoke Detectors will generally
detect a fire far sooner than heat detectors. It is
therefore preferable to fit Smoke Detectors unless there
is any possibility of false or unwanted alarms. It
is not advisable for example to fit a Smoke Detector
in a kitchen as anybody burning toast would cause an
unwanted alarm. Heat Detectors should be fitted in
boiler rooms, generator rooms, garages and dusty areas.
The products of combustion produced by a boiler, a leaky
exhaust on a generator or exhaust fumes from a vehicle
could all cause a smoke detector to operate and produce
an unwanted alarm.
Fixed Temperature Heat
Detectors should be installed in areas where one would
normally expect a sudden rise in temperature for instance
kitchens and boiler rooms.
Rate of Rise Heat Detectors
should be installed where Smoke Detectors would be unsuitable
but one would not expect a sudden rise in temperature
for instance, garages, car parks, dusty workshops etc.
There are two basic types
of Point Smoke Detectors:
|
1 |
Ionisation chamber Smoke Detectors which
are very sensitive to smoke with small particles ie: fresh
cellulosic smoke and the source of almost invisible smoke
one gets with burning paper and spirit. They are relatively
insensitive to smoke with large particles for example,
smoke produced by burning plastics or stale smoke. |
2 |
Optical Smoke Detectors are sensitive to
optically dense smoke ie: smoke with large particles and
they are relatively insensitive to optically thin smoke. |
Some countries ie: Italy, Japan, Qatar only
use Optical Smoke Detectors and within parts of the Middle
and Far East, only Ionisation Detectors are used. Within
the UK systems can comprise of a mixture of the two.
The demise of most people is caused by thick dense choking
smoke which is normally a greater problem than getting
burnt. For this reason Optical Detectors are normally
used on escape routes such as corridors and stairwells.
Ionisation Smoke Detectors are normally fitted within
office and other general areas. |
Siting
of Detectors
In a building the greatest
concentration of Smoke and Heat will generally collect
at the highest parts of the enclosed areas and it is
here therefore, that the detectors should normally be
sited.
Smoke
Detectors
Smoke Detectors should be
sited so that the sensing element is not less than 25mm,
nor more than 600mm below the ceiling or roof. If a
protected space has a pitched or northern light roof,
then Smoke Detectors should be installed in each apex.
The maximum horizontal
distance between any point in the area being protected
and the nearest detector should be as follows:
Under flat horizontal ceilings
and corridors more than 5m wide, then the maximum distance
for Point Type Smoke Detectors should not exceed 7.5m.
The maximum area of coverage of a Point Smoke Detector
is 100 square metres. On the rear of all Photain Smoke
Detector Data Sheets, a diagram showing the relevant
coverage they provide is shown.
In corridors the number
of detectors required depends on the corridor width.
When installing Smoke Detectors the following data can
be used:
|
Corridor
Width (m)
|
Allowable
Radius of Cover (m)
|
Maximum
Spacing between Detectors (m)
|
1.2
|
9.4
|
18.76
|
1.6
|
9.2
|
18.33
|
2.0
|
9.0
|
17.89
|
2.4
|
8.8
|
17.44
|
2.8
|
8.6
|
16.97
|
3.2
|
8.4
|
16.49
|
3.6
|
8.2
|
16.00
|
4.0
|
8.0
|
15.49
|
4.4
|
7.8
|
14.97
|
4.8
|
7.6
|
14.42
|
5.0 or more
|
7.5
|
|
The maximum height that smoke detectors should be installed
at is as follows:
Point Smoke Detectors 10.5m
Optical Beam Smoke Detectors
25m
|
If detectors are to be fitted
in the apex of a pitched or north light roof then a
row of detectors should be sited within the apex. One
row of detectors should be sited at the highest point
a minimum distance of 0.5m from the vertical wall.
Add to the maximum horizontal distance 1% for each degree
of the slope up to a maximum of 25%. For instance a
point type detector at the apex of a 20 degree slope
would work out as follows: 20% of 7.5m = 1.5m. Therefore
the maximum distance between detectors = 7.5 + 1.5 =
9m. The maximum area of coverage may also be increased
proportionally.
Where the passage of Smoke
or Hot Gases from a position to a detector is likely
to be disturbed by a ceiling obstruction such as a beam
having a depth greater than 150mm but less than 10%
of the height of the ceiling, then the horizontal distance
should be decreased by twice the depth of the obstruction.
For instance for a Point Type Smoke Detector obstructed
by a 200mm depth beam then the maximum distance between
detectors = 0.2m x 2 = 0.4m.
7.5m - 0.4m = 7.1m.
Where a ceiling obstruction,
such as a beam is greater than 10% of the height of
the ceiling then the area either side of the obstruction
should be considered as separate rooms.
Ceiling beams less then
150mm in depth can be ignored.
Optical beam smoke detectors
are useful for covering large unobstructed roof areas
such as those found in most warehouses. They can be
quite cost effective as one smoke beam can provide the
coverage of many individual point detectors. A smoke
beam typically comprises of a Projector, a Receiver,
a Remote Manual Reset Unit and a Local Power Supply
with battery standby. Optical Beam Smoke Detectors
should be mounted as follows: (m = Metres)
|
·
|
The minimum height above floor level |
= 2.7m |
·
|
Maximum height above floor level |
= 25m |
·
|
Minimum Optical Beam length |
= 10m |
·
|
Maximum Optical Beam length |
= 100m |
·
|
Minimum distance of Optical Beam
From a flat ceiling or apex |
= 0.3m |
·
|
Maximum horizontal distance between Optical
Beams measured at right angles to a Beam
|
= 14m |
·
|
The Maximum horizontal distance between
Optical Beam and an adjacent wall or partition |
= 7m |
Heat
Detectors
Heat Detectors should be
sited so that the heat sensitive element is not less
than 25mm, nor more than 150mm below the ceiling or
the roof.
The maximum horizontal
distance between any point in the area being protected
and the nearest detector should be as follows:
Under flat horizontal ceilings
and corridors more than 5m wide then the maximum distance
between any heat detector and any wall or partition
should be 5.3m.
The maximum area of coverage
per heat detector is 50 square metres.
On the rear of all Photain
Heat Detector Data Sheets, a diagram showing the relevant
coverage they provide is shown.
There is also information
regarding detector coverage in corridors using Heat
Detectors. As Heat Detectors are very seldom used in
corridors then please consult British Standard BS5839
Part 1, should you require this information.
The maximum height that
Heat Detectors should be installed at are as follows:
Grade 1 Heat Detector 9m
Grade 2 Heat Detector 7.5m
Grade 3 Heat Detector 6m
High Temperature Heat Detectors
6m
|
Return to Top
|