This table
provides suggested air changes per hour (ACH)
under normal conditions.
Assembly
rooms |
4
- 8 |
Bakeries |
20
- 30 |
Banks/Building
Societies |
4
- 8 |
Billiard
Rooms * |
6
- 8 |
Boiler
Rooms |
15
- 30 |
Canteens |
8
- 12 |
Changing
Rooms Main area |
6
- 10 |
Changing
Rooms Shower area |
15
- 20 |
Churches |
1
- 3 |
Cinemas
and theatres * |
10
- 15 |
Club
rooms |
12
minimum |
Compressor
rooms |
10
- 20 |
Conference
rooms |
8
- 12 |
Dairies |
8
- 10 |
Dance
halls |
12
minimum |
Dental
surgeries |
12
- 15 |
Dye
works |
20
- 30 |
Electroplating
shops |
10
- 12 |
Engine
rooms |
15
- 30 |
Entrance
halls & corridors |
3
- 5 |
Factories
and workshops |
8
- 10 |
|
|
Foundries |
15
- 30 |
x |
Glasshouses |
25
- 60 |
|
Gymnasiums |
6
minimum |
|
Hospitals
- sterilising |
15
- 25 |
|
Kitchens
- domestic |
15
- 20 |
|
Kitchens
- commercial # |
30
minimum |
|
Laboratories |
6
- 15 |
|
Lavatories |
6
- 15 |
|
Lecture
theatres |
5
- 8 |
|
Libraries |
3
- 5 |
|
Mushroom
houses |
6
- 10 |
|
Paint
shops (not cellulose) |
10
- 20 |
|
Photo
& X-ray darkrooms |
10
- 15 |
|
Public
house bars |
12
minimum |
|
Recording
control rooms |
15
- 25 |
|
Recording
studios |
10
- 12 |
|
Shops
and supermarkets |
8
- 15 |
|
Squash
courts |
4
minimum |
|
Swimming
baths |
10
- 15 |
|
Welding
shops |
15
- 30 |
|
*
Increase by 50% where heavy smoking occurs or if the room
is underground.
# Some commercial kitchens may require higher ventilation
rates, based on cooking equipment in use.
|