2.5 - Low voltage generating sets
A
completely new Section of 24 Regulations was introduced
by the 1997 amendments dealing with low voltage generating
sets. This set of Regulations was numbered Section 551,
the existing [551 - Transformers] being renumbered as 555
to accommodate it.
Where
low voltage or extra-low voltage generating sets are used
to power an installation, (a) as the sole means of supply,
or (b) as a backup in case of failure of the supply, or
(c) for use in parallel with the supply, these Regulations
apply. Self-contained systems, operating at extra-low voltage,
which include the source of energy (usually batteries) as
well as the load are not covered.
Generating
sets, for the purpose of these Regulations, include not
only rotating machines powered by combustion engines, turbines
and electric motors, but also photovoltaic cells (which
convert energy from light into electricity) and electrochemical
accumulators or batteries. Protection of circuits fed from
generators must be no less effective than those applying
to mains-fed systems. Voltage and frequency variations are
much more likely with generators than with a mains supply,
and it must be ensured that they do not cause danger or
damage t6 the equipment.
Protection
of persons and of equipment must be at least as effective
in the case of an installation fed permanently or occasionally
by a generating set as for a mains-fed installation. Special
requirements for bonding apply where static invertors are
used. A static invertor is an electronic system which produces
an ac supply at a given voltage, frequency and waveform
from a dc source (often from a battery). When two or more
generating sets operate in parallel, circulating harmonic
currents are a possibility. Such currents are at frequencies
which are multiples of the normal supply frequency, and
will possibly result in overloading of the connecting cables
unless steps are taken to reduce or remove them. When not
intended to run in parallel with the mains supply, for example
when used as a standby system. interlocks and switching
must be provided to ensure that parallel operation is not
possible.
When
a generating set is intended as a standby system for use
in place of the mains supply in the event of failure, precautions
must be taken to ensure that the generator cannot operate
in parallel with the mains. Methods include an interlock
between the operating systems of the changeover switches,
a system of locks with a single transferable key, a three-position
break-before-make changeover switch, or an automatic changeover
switch with an interlock.
Where
generators are intended to operate in parallel with the
mains supply, the Supply Company must be consulted to ensure
that the generator is compatible in all respects (including
power factor, voltage changes, harmonic distortion, unbalance,
starting, synchronising and voltage fluctuation) with the
mains supply. In the event of any of the above parameters
becoming incompatible with the mains supply, the generating
set must be automatically disconnected. Such disconnection
must also occur if its voltage or frequency stray outside
the limits of protection. It must be possible to isolate
the generating set from the mains supply, and that means
of isolation must always be accessible to the supply company.