3.1 - Introduction
Electrical installations must
be protected from the effects of short circuit and over-load.
In addition, the people using the installations, as well
as the buildings containing them, must be protected from
the effects of fire and of other hazards arising from faults
or from misuse.
Not only must automatic fault protection
of this kind be provided, but an installation must also
have switching and isolation which can be used to control
it in normal operation, in the event of emergency, and when
maintenance is necessary.
This Chapter will consider those regulations
which deal with the disconnection of circuits, by both manual
and automatic means, the latter in the event of shock, short
circuit or overload. It does not include the Regulations
which concern automatic disconnection in the event of an
earth fault: these are considered in
{Chapter
5}.
In order that anyone operating or testing
the installation has full information concerning it, a diagram
or chart must be provided at the mains position showing
the number of points and the size and type of cables for
each circuit, the method of providing protection from direct
contact (see
{3.4.5}) and details of any circuit in which
there is equipment, such as passive infra-red detectors
or electronic fluorescent starters, vulnerable to the high
voltage used for insulation testing.
|