4.3.12 - Harmonic currents
and neutral conductors
A perfectly balanced three-phase system
(one with all three phase loads identical in all respects)
has no neutral current and thus has no need of a neutral
conductor. This is often so with motors, which are fed through
three core cables in most cases.
Many three-phase loads are made up of single-phase
loads, each connected between one line and neutral. It is
not likely in such cases that the loads will be identical,
so the neutral will carry the out-of-balance current of
the system. The greater the degree of imbalance, the larger
the neutral current.
Some three-phase four-core cables have
a neutral of reduced cross-section on the assumption that
there will be some degree of balance. Such a cable must
not he used unless the installer is certain that severe
out-of-balance conditions will never occur. Similar action
must be taken with a three-phase circuit wired in single-core
cables. A reduced neutral conductor may only be used where
out-of-balance currents will be very small compared to the
line currents.
A problem is likely to occur in systems
which generate significant third harmonic currents. Devices
such as discharge lamp ballasts and transformers on low
load distort the current waveform. Thus, currents at three
times normal frequency (third harmonics) are produced, which
do not cancel at the star point of a three-phase system
as do normal frequency currents, but add up, so that the
neutral carries very heavy third harmonic currents. For
this reason, it is important not to reduce the cross-sectional
area of a neutral used to feed discharge lamps (including
fluorescent lamps).
In some cases the neutral current may be
considerably larger than the phase currents. Where the load
concerned is fed through a multi-core cable, it may be prudent
to use five-core (or even six-core) cables, so that two
(or three) conductors may be used in parallel for the neutral.
In some cases it may be necessary to insert
overload protection in a neutral conductor. Such protection
must be arranged to open all phase conductors on operation,
but not the neutral. This clearly indicates the use of a
special circuit breaker.
It is very important that the neutral of
each circuit is kept quite separate from those of other
circuits. Good practice suggests that the separate circuit
neutrals should be connected in the same order at the neutral
block as the corresponding phase conductors at the fuses
or circuit breakers.