5.4.4 - Protective conductor cross-section assessment
A fault current will flow when an earth
fault occurs. If this current is large enough to operate
the protective device quickly, there is little danger of
the protective conductor and the exposed conductive parts
it connects to earth being at a high potential to earth
for long enough for a dangerous shock to occur. The factors
determining the fault current are the supply voltage and
the earth-fault loop impedance (see{5.3}).
The earth fault results in the protective
conductors being connected in series across the supply voltage
{Fig 5.16}. The voltage above earth of the earthed metalwork
(the voltage of the junction between the protective and
phase conductors) at this time may become dangerously high,
even in an installation complying with the Regulations.
The people using the installation will be protected by the
ability of the fuse or circuit breaker in a properly designed
installation to cut off the supply before dangerous shock
damage results.
Fig 5.16
- The effect of protective conductor resistance on
shock voltage
a) effective resistance
of a ring circuit protective conductor
b) potential differences across healthy protective
conductor in the event of an earth fault
Table 5.7 - Main earthing
and main equipotential bonding conductor
----------------- sizes
for TN-S and TN-C-S supplies |
Phase conductor (or neutral for
PME supplies )
|
Earthing conductor (not buried or
protected against mechanical damage)
|
Main equipotential bonding conductor
for PME supplies
|
Main equipotential bonding conductor
|
csa mm²
|
csa mm²
|
csa mm²
|
csa mm²
|
4
|
4
|
6
|
10
|
6
|
6
|
6
|
10
|
10
|
10
|
6
|
10
|
16
|
16
|
10
|
10
|
25
|
16
|
10
|
10
|
35
|
16
|
10
|
10
|
50
|
25
|
16
|
16
|
70
|
35
|
16
|
25
|
Remember that lower fault levels
result in a longer time before operation of the protective
device. Since the cross-sectional area of the protective
conductor will usually be less than that of live conductors,
its temperature, and hence its resistance, will become higher
during the fault, so that the shock voltage will be a higher
proportion of the supply potential (see {Fig 5.16}).
{Fig
5.16} shows the circuit arrangements, with some typical
phase- and protective-conductor resistances. In this case,
a shock voltage of 140 V will be applied to a person in
contact with earthed metal and with the general mass of
earth. Thus, the supply must he removed very quickly. The
actual voltage of the shock depends directly on the relationship
between the phase conductor resistance and the protective
conductor resistance. If the two are equal, exactly half
the supply voltage will appear as the shock voltage.
For socket outlet circuits, where the shock
danger is highest, the maximum protective conductor resistance
values of {Table
5.3} will ensure that the shock voltage never exceeds
the safe value of 50 V. If the circuit concerned is in the
form of a ring, one quarter of the resistance of the complete
protective conductor round the ring must not be greater
than the {Table
5.3} figure. The reason for this is shown in {Fig 5.16(a)}.
This assumes that the fault will occur exactly at the mid
point of the ring. If it happens at any other point, effective
protective conductor resistance is lower, and safer, than
one quarter of the total ring resistance.
{Table 5.7} allows selection (rather than
calculation) of sizes for earthing and bonding conductors.
The rules applying to selection are:
For phase conductors up to 16 mm², the
protective conductor has the same size as the phase conductor.
For phase conductors from 16 mm² to 35
mm², the protective conductor must be 16 mm²
For phase conductors over 35 mm², the protective
conductor must have at least half the c.s.a. of the phase
conductor. The minimum cross-sectional area of a separate
CPC is 2.5 mm² if mechanically protected and 4mm² if not.
Note that Regional Electricity Companies
may require a minimum size of earthing conductor of 16 mm²
at the origin of the installation. Always consult them before
designing an installation.