8.5.4 - Tests for electrical separation of circuits
This section is concerned with tests necessary
to ensure the safety of separated extra-low voltage (SELV),
protective extra-low voltage (PELV) and functional extra-low
voltage (FELV) circuits which are explained in {7.16}.
In general, the requirement is a thorough inspection to
make sure that the source of low voltage (most usually a
safety isolating transformer) complies in all respects with
the British Standard concerned, followed by an insulation
test between the extra-low voltage and low voltage systems.
The test is unusual in that a 500 V dc supply (from an insulation
resistance tester) must be applied between the systems for
one minute, after which the insulation resistance must not
be less than 5 MOhms for SELV or PELV systems, or 0.5 MOhms
for FELV systems. A further test at 3750 V dc for one minute
is passed if no flashover occurs. This test in particular
can be dangerous, and special care should be taken.
For SELV and FELV circuits, additional
inspection must ensure that the low voltage requirements
(not exceeding 50 V ac or 120 V dc) are met. If the voltage
exceeds 25 V ac or 70 V dc (60 V ripple-free), barriers
and enclosures must be tested to IP2X (see
{Table 2.1})and a 500 V dc insulation test applied for
one minute between the live conductors and metal foil wrapped
round the insulation should produce a result of at least
0.5 MOhms
When insulation testing on electrically
isolated circuits or on equipment which might be damaged
by the test voltage, phase and neutral must be connected
together and the test applied between them and earth.
|