5.6.2 - Increased fire risk
As with other systems of earth-fault protection,
PME does not prevent a fault occurring, but will ensure
that the fault protection device operates quickly when that
fault appears. For example, if a fault of 2 Ohms resistance
occurs in a 240 V circuit protected by a 20 A semi-enclosed
fuse in a system with an earth-fault loop impedance of 6
Ohms, the fault current will be 240/(2 + 6) A = 240/8 A
= 30 A. The fuse would not blow unless the circuit were
already loaded, when load current would add to fault current.
If the circuit were fully loaded with a load current of
20 A, total current would be 50 A and the fuse would blow
after about 18 s. During this time, the power produced in
the fault would be:
P = I²R =
30²x6 = 5400W or 5.4kW
|
This could easily start a fire. If, however,
the earth-fault loop impedance were I Ohm, current would
be 80 A and the fuse would blow in about 1.6 s and limit
the energy in the fault circuit.
|