16th Edition (reference only) – NOW superseded by the 17th Edition IEE Regulations.

chapter 5
Earthing

chapter 6
Circuits

Earthing
  5.1 - The earthing principle 5.6 - Protective multiple earthing (PME)
  5.2 - Earthing Systems 5.7 - Earthed concentric wiring
  5.3 - Earth fault loop impedance 5.8 - Other protection methods
5.4 - Protective conductors 5.9 - Residual current devices (RCDs)
5.5 - Earth electrodes

5.10 - Combined functional and protective
---------earthing


5.6.2 - Increased fire risk

As with other systems of earth-fault protection, PME does not prevent a fault occurring, but will ensure that the fault protection device operates quickly when that fault appears. For example, if a fault of 2 Ohms resistance occurs in a 240 V circuit protected by a 20 A semi-enclosed fuse in a system with an earth-fault loop impedance of 6 Ohms, the fault current will be 240/(2 + 6) A = 240/8 A = 30 A. The fuse would not blow unless the circuit were already loaded, when load current would add to fault current. If the circuit were fully loaded with a load current of 20 A, total current would be 50 A and the fuse would blow after about 18 s. During this time, the power produced in the fault would be:

P = I²R = 30²x6 = 5400W or 5.4kW

This could easily start a fire. If, however, the earth-fault loop impedance were I Ohm, current would be 80 A and the fuse would blow in about 1.6 s and limit the energy in the fault circuit.

 

Return to top of page

Extracted from The Electricians Guide Fifth Edition
by John Whitfield

Published by EPA Press Click Here to order your Copy.

Click here for list of abbreviations