|  
                    6.2.3 -  Applied diversity
 Apart from indicating that diversity and 
                      maximum demand must be assessed, theRegulations themselves give little help. Suggestions 
                      of values for the allowances
 for diversity are given in {Table 6.2}.
 Distribution boards must not have diversity applied 
                      so that they can carry the total load connected to them.
 Example 6.1A shop has the following single-phase loads, which 
                      are balanced as evenly as possible across the 415 V three-phase 
                      supply.
 2 x 6 kW and 7 x 3kw thermostatically controlled 
                      water heaters2 x 3 kW instantaneous water heaters
 2 x 6 kW and 1 x 4 kW cookers
 12 kW of discharge lighting (Sum of tube ratings)
 8 x 30 A ring circuits feeding 13 A sockets.
 Calculate the total demand of the system, 
                      assuming that diversity can be applied. Calculations will 
                      be based on {Table 6.2}. The single-phase voltage for a 415V three-phase 
                      system is 415/Ö 3 = 240 
                      V. All loads with the exception of the discharge 
                      lighting can be assumed to be at unity power factor, so 
                      current may be calculated from Thus the current per kilowatt 
                      will be    
                       
                        | Table 6.2 - Allowance for diversity |   
                        | Note the following abbreviations 
                            :X is the full load current of the largest 
                            appliance or circuit
 Y is the full load current of the second 
                            largest appliance or circuit
 Z is the full load current of the remaining 
                            appliances or circuits
 |   
                        | Type of final circuit |  | Type of premises |  |   
                        |  | Households | Small shops, stores, offices | Hotels, guest houses |   
                        | Lighting | 66% total demand | 90% total demand | 75% total demand |   
                        | Heating and power | 100% up to 10 A + 50% balance | 100%X + 75%(Y+Z) | 100%X + 80%Y + 60%Z |   
                        | Cookers | 10 A + 30% balance + 5 A for socket | 100%X + 80%Y + 60%Z | 100%X + 80%Y + 60%Z |   
                        | Motors (but not lifts) |  | 100%X + 80%Y + 60%Z | 100%X + 50%(Y+Z) |   
                        | Instantaneous water heaters | 100%X + 100%Y + 25%Z | 100%X + 100%Y + 25%Z | 100%X + 100%Y + 25%Z |   
                        | Thermostatic water heaters | 100% | 100% | 100% |   
                        | Floor warming installations | 100% | 100% | 100% |   
                        | Thermal storage heating | 100% | 100% | 100% |   
                        | Standard circuits | 100%X + 40%(Y+Z) | 100%X + 50%(Y+Z) | 100%X + 50%(Y+Z) |   
                        | Sockets and stationary equip. | 100%X + 40%(Y+Z) | 100%X + 75%(Y+Z) | 100%X + 75%Y + 40%Z |  Water 
                      heaters (thermostatic) 
                       
                        | No diversity is allowable, so the 
                          total load will be: |   
                        | (2 x 6) + (7 x 3) kW = 12 + 21kw 
                          = 33kw |   
                        | This gives a total single-phase current 
                          of I = 33 x 4.17 = 137.6 A |  
 Water heaters (instantaneous) 
                       
                        | 100% of largest 
                          plus 100% of next means that in effect there is no allowable 
                          diversity. |   
                        | Single-phase current thus | = 2 x 3 x 4.17  = | 25.0 
                          A |    Cookers 
                       
                        | 100% of largest | = 6 x 4.17A = | 25.0 A |   
                        | 80% of second | = 80 x 6 x 4.17A = | 20.0 A |   
                        |  | =100 |  |   
                        | 60% of remainder | = 60 x 4 x 4.17 
                          A = | 10.0 A |   
                        |  | =100 |  |   
                        | Total for cookers | =  | 55.O A |  
 Discharge lighting 
                       
                        | 90% of total which must 
                          be increased to allow for power factor and control gear 
                          losses. |   
                        |  |  |  |   
                        | Lighting current | = 12 x 4.17 x 1.8 x 90 = | 81.1 A |   
                        |  | 100 |  |  
 Ring circuits 
                       
                        | First circuit 100%, 50 
                          current is 30 A |   
                        | 75% of remainder | = 7 x 30 x 75 = | 157.5 A |   
                        |  | 100 |  |   
                        | Total current demand 
                          for ring circuits = | 187.5 A |   
                        | Total single phase current 
                          demand = | 486.2 A |   
                        | Since a perfect balance 
                          is assumed, three phase line current = | 486.2 A |   
                        |  |  | =3 |   
                        |  | =  | 162 A |  
 |