3.7.1 - Introduction
The overload currents considered in the
previous section are never likely to be more than two to
three times the normal rated current. Fault currents, on
the other hand, can well be several hundreds, or even several
thousands of times normal. In the event of a short circuit
or an earth fault causing such current, the circuit must
be broken before the cables are damaged by high temperatures
or by electromechanical stresses. The latter stresses will
be due to the force on a current carrying conductor which
is subject to the magnetic field set up by adjacent conductors.
This force is proportional to the current, and to the magnetic
field strength. Since the field strength also depends on
the current, force is proportional to the square of the
current. If the current is one thousand times normal, force
will be one million times greater than usual! Fault protection
must not only be able to break such currents, but to do
so before damage results. Abrasion of cable insulation by
movement is usually prevented by normal fixings or by being
enclosed in conduit or trunking. Support must he provided
to cables in busbar chambers.
|