7.17.2 - The marina electrical installation
As for caravans, the neutral of a PME system
must not be connected to the earthed system of a boat so
that the hazards which follow the loss of continuity in
the supply PEN conductor are avoided. This rules out the
use of PME supplies for marinas. Where this is the supply
provided, it must be converted to a TI' system at the main
distribution board by provision of an separate earth electrode
system of driven rods or buried mats with no overlap of
resistance area with any earth associated with the PME supply.
If the marina is large enough, it may be that the supply
company will provide a separate transformer and a TN-S system.
Shock protection
Protection by obstacles or by placing out of reach
are not acceptable as methods of preventing direct contact.
A non-conducting location must not be used for protection
from indirect contact. Where a TN-S system is used, indirect
protection must be provided by an RCD which breaks all poles
unless protection is provided by an on-shore isolating transformer.
Wiring Systems
No aluminium cables may be used in marina installations.
Acceptable cables for fixed wiring are:
- those with
thermoplastic, thermosetting or elastomeric insulation and
sheath installed
- in non-flexible non-metallic
conduit, or in heavy-duty galvanised conduit,
- mineral insulated cable with extruded p.v.c. covering,
- armoured cables with sheaths of thermoplastic or
elastomeric material.
A boat will move relative to
the land due to wind and waves. Cables must be selected
and installed so that mechanical damage as a result of tidal
and other movement of floating structures is prevented.
Cabling to bridge ramps, pontoons and movable jetties must
be carried out in flexible cables with EPR or thermosetting
insulation and sheaths. Overhead lines are not permitted.
Conduit installations must be provided with apertures or
holes to allow for drainage.
It should be noted that p.v.c. cables are
not usually suitable for continuous immersion in water.
Cables intended to be permanently immersed to a depth of
4 m or more should be sheathed with lead; where the immersion
is less than 4 m, cables should be armoured and provided
with polythene bedding and outer sheath. Due to possible
problems with corrosion, cable armouring must not be relied
upon as a circuit protective conductor. A separate CPC must
be provided to which the armouring is securely connected.
Cable terminations must be protected against corrosion by
selection of suitable materials, or by the application of
grease or mastic or paint. Buried cables will be required
on-shore. It must be remembered that such situations will
be subjected to very weighty traffic as boat trailers are
moved. Unless the buried cables are above the water table
they must be suitable for continuous immersion.
Distribution boards
Distribution boards must be protected to IP44, and
against the ingress of dust and sand. Construction of glass
reinforced plastic (GRP) gives better corrosion protection
than galvanised steel. Where mounted on fixed jetties, they
must be at a minimum of 1 m above the high water level;
on floating jetties, they must be at least 750 mm above
the water. Boards must be fitted with locks to prevent unauthorised
access, and with internal barriers to prevent contact with
live parts (to IP 2X) when the doors are open. Low power
heaters may be needed within the boards to prevent excessive
condensation.
Socket outlets
A common installation method is to provide a feed
from the shore to a floating pontoon via a bridge or ramp,
and then to equip the pontoon with socket outlets to feed
the craft moored to it. Socket outlets may be single- or
three-phase. Where multiple single-phase sockets are installed
on the same pontoon, they must all be connected to the same
phase of the supply unless fed through isolating transformers.
All socket outlets must be to BS EN 60309-2 with keyways
at 6R, protected to IPX4 minimum, coloured red if three-phase
and blue if single-phase. Single-phase sockets are usually
rated at 16 A and three-phase at 32 A, although higher ratings
may be installed where the need arises. Socket outlets should
be positioned as close as possible to the berth of the vessel
they feed, with a minimum of one socket per berth, although
up to six sockets may be provided in a single enclosure.
Each socket outlet must be provided with a means of isolation
which breaks all poles on T[ systems, and must be protected
by an overcurrent device such as a fuse or a circuit breaker.
Groups of socket outlets must be RCD protected. Each socket
or group of sockets must be provided with a durable and
legible notice giving instructions for the electricity supply
(see {Table 7.10}); alternatively the notice must be placed
in a prominent position or must be issued to each berth
holder.
Table 7.10 - Instructions for
electricity supply
|
Berthing instructions
for connection to the shore supply |
This marina provides
power for use on you leisure craft with a direct connection
to the shore supply which is connected to earth. Unless you have an isolating transformer fitted
on board to isolate the electrical system of your craft
from the shore supply system, corrosion through electrolysis
could damage your craft or surrounding craft. |
ON ARRIVAL |
1 |
Ensure that the supply
is switched off before inserting the craft plug. |
2 |
The supply to the berth
is ***V, **Hz. The socket outlet will accommodate a
standard marine plug coloured ****. |
3 |
For safety reasons, your
craft must not be connected to any other socket outlet
than that allocated to you and the internal wiring on
your craft must comply with the appropriate standards. |
4 |
Every effort must be
made to prevent the connecting flexible three-core cable
from falling into the water if it should become disengaged.
For this purpose, securing hooks are provided alongside
socket outlets for anchorage at a loop of tie cord. |
5 |
For safety reasons, only
one leisure-craft connecting cable may be connected
to any one socket outlet. |
6 |
The connecting flexible
cable must be in one length, without signs of damage,
and not containing joints or other means to increase
its length. |
7 |
The entry of moisture
and salt into the leisure-craft inlet socket may cause
a hazard. Examine
carefully and clean the plug and socket before connecting
the supply. |
8 |
It is dangerous to attempt
repairs or alterations, if any difficulty arises, contact
the marina management. |
BEFORE LEAVING |
1 |
Ensure that the supply
is switched off before the connecting cable is disconnected
and any tie cord loops are unhooked. |
2 |
The connecting flexible
cable should be disconnected first from any marina socket
outlet and then from the leisure craft inlet socket.
Any cover that may be provided to protect the
inlet from the weather should be securely replaced. The connecting flexible cable should be coiled
up and stored in a dry location where it will not be
damaged. |
**** Appropriate figures and colours
must be inserted
either 220-250 V blue,
or 380-415 V red.
|
Inspection
and testing
Inspection and testing must be carried out in full
accordance with BS 7671 (see
{Chapter
8}).
Periodic testing must be at least annually, but may
need to be more frequent if the marina is exposed
or subject to misuse.