7.19.2 - Recommendations
for exhibitions, shows and stands
Shock protection
Protection against direct contact (see
{3.4.5}) by means of obstacles and placing out of reach
must not be used, and neither must non-conducting location
and earth-free equipotential bonding be used as protection
against indirect contact (see
{3.4.6}). Automatic disconnection of the supply is the
preferred method, but because of the difficulty of bonding
all accessible extraneous conductive parts, PME supplies
(TN-C-S system) must not be used for temporary or outdoor
installations. A TN-S system (where the supply company provides
an earth) could be used, but a TT system (earthed using
an electrode) is preferable. The maximum disconnection times
are reduced to 0.2 s for 240 V and to 0.05 5 for 415 V systems,
which means that the earth fault loop impedance values are
reduced to those shown in {Table
7.4} for agricultural applications. Livestock are often
present at agricultural shows. In this case, supplementary
bonding must connect all exposed conductive parts and extraneous
conductive parts which can be touched by them.
Distribution circuits which are at an increased
risk of damage must be protected by an RCD with a 300 to
500 mA rating; to provide discrimination with other RCDs
protecting final circuits, they should be time delayed.
All final circuits for socket outlets must be protected
by RCDs rated at 30 mA. Final circuits for lighting which
are accessible to the public must also be protected by 30
mA RCDs. However, loss of light in a crowded space is likely
to cause a serious hazard, and such areas should be fed
from at least two separate circuits with separate RCD protection.
Extraneous conductive parts on vehicles, wagons, caravans
etc. must be bonded to the protective system using conductors
of not less than 4 mm².
Fire protection
Because of the increased risk of fire and burns in
these locations, it is very important to follow the advice
given in {3.5}.
Where SELV or PELV Systems are used (see{3.4.4})
they must be insulated and tested as if they were 240 V
circuits. Stored material, such as cardboard boxes and fodder,
are a special fire hazard. Remotely or automatically controlled
motors must be fitted with manual reset controls against
excess temperature and must be accessible only to skilled
persons. Lighting equipment, such as incandescent lamps,
spotlights, projectors, etc., must be suitably positioned
and guarded to prevent overheating to themselves or of.
adjacent surfaces. Sufficient ventilation must he provided
to prevent the build-up of heat.
Isolation
Every separate temporary structure and each distribution
circuit supplying outdoor installations must he provided
with its own easily accessible and clearly identified means
of isolation.
Equipment
Equipment must he mounted away from positions which
may not be weather-proof. Tent poles are the most obvious
place to mount equipment, but are often the weak point in
the weather tightness of temporary structures. Switchgear
should be mounted in closed cabinets which can only be opened
by a key or a tool, but isolators must be always accessible.
Wiring Systems
The types and protection of cables is of particular
importance, as is the current carrying capacity. Wherever
there is a risk of damage, mechanical protection or armoured
cables should be used - trailing flexibles should never
exceed 2 m in length to reduce the risk of tripping and
of damage to the equipment and terminations. Underground
cables should be clearly marked, hearing in mind that structure
support pins may be 1 m long. Where a fire alarm is not
installed, cables must be of the flame retardant, low smoke
type or enclosed in conduit or trunking to prevent the spread
of fire. There must be no joints in cables except as a connection
into a circuit. Where lurninaires are mounted below 2.5
m (within arm's reach) they must be firmly fixed and carefully
sited to reduce danger to people and the possibility of
fire. Electric motors must have isolation equipment breaking
all poles, and must be provided with adjacent emergency
stop systems. Socket outlets are subject to particular abuse
by users in these situations. They should:
1. - be adequate in number,
2. - preferably not he floor mounted,
but if so, must be mechanically protected and waterproof,
3.
- have no more than one flexible cable or cord connected
to each plug,
4. - never have multiway plug-in
adapters connected, and
5. -
have no more than one portable trailing block multiway
socket connected by means of a
----- flexible cord not exceeding
2 m in length.
Safety systems
Where a generator is used to supply the temporary
installation, there must be full earthing using separate
earth electrodes. For TN systems, all exposed conductive
parts must be bonded back to the generator. Where the exhibition
is held in a building, care must be taken to ensure that
temporary structures do not impede escape routes. Where
an exhibition is constructed out-of-doors, a fire alarm
system must be installed to enclosed areas, and emergency
lighting must be provided for escape routes.
Inspection and testing
The electrical installations of all stands must be
re-tested on site after each assembly. Exhibitors and stall
holders must be encouraged to visually check electrical
equipment for damage on a daily basis.