|  
                    
                    7.2.2A - Bath and shower room requirements (amended)  
                  The revised Regulations for bath and shower rooms are based 
                    on the dimensions of four zones into which the space is divided. 
                   
                   Zone O.  
                    is the interior of the bathtub or the shower basin. In those 
                    cases where a shower has no basin, the zone extends 50mm above 
                    the floor and includes the volume within the vertical surface 
                    at a radius of 1.2m from the water outlet position of a demountable 
                    shower head, or at a radius of 0.6m from the position of a 
                    fixed shower head.  
                   Zone 1.  
                    extends from Zone 0 up to 2.25m above the floor, and outwards 
                    to the extent of the bath or basin, or the extent of Zone 
                    0 as defined above where there is no shower basin. It includes 
                    the space below a bath or shower tub or basin where that space 
                    is accessible without the use of a tool.  
                   Zone 2.  
                    extends outside Zone 1 for 0.6m horizontally and up to a height 
                    of 2.25m. If the ceiling height is more than 2.25m, the space 
                    above Zone 1 up to 3m is also zone 2 
                  Zone 3. 
                    extends outside Zone 2 for 2.4m horizontally and up to a height 
                    of 2.25m. If the ceiling height is more than 2.25m, the space 
                    above Zone 2 up to 3 m is also Zone 3 
                   
                    If the space under a bathtub or shower basin can only be accessed 
                    with the use of a tool, that space is outside the zones. If 
                    no tool is required the space is Zone 1.  
                  The extent of the zones is shown in Figs 7.1b) to 7.1g) in 
                    diagrams which are not to scale.  
                  
                  Figure 7.1b) - Zones for a bathroom (plan). 
                     
                    Note that the same zones apply to a shower room with a shower 
                    basin.  
                  
                  Figure 7.1c) - Zones for a bathroom (elevation). 
                     
                    Note that the same zones apply to a shower room with a shower 
                    basin.  
                  
                  Figure 7.1d) - Zones for a shower with 
                    no basin and a fixed head.  
                  
                  Figure 7.1e) - Zones for a shower room 
                    (elevation) 
                    without a basin and having a fixed showerhead. 
                  Where SELV (safety extra-low voltage, see (3.4.4) 
                    is used, protection against direct contact must be provided 
                    by barriers or enclosures to IP2X (no finger contact) or by 
                    insulation which will withstand 500 V a.c for one minute. 
                    PELV (which is earthed SELV) is not permitted in bath and 
                    shower rooms. Local supplementary equipotential bonding must 
                    be installed to connect together the exposed conductive parts 
                    of Class 1 and Class 11 equipment in Zones 1,2, and 3 together 
                    with extraneous conductive parts, such as metal baths and 
                    shower trays, metallic pipes for water, gas, central heating, 
                    air conditioning. etc in all zones. Accessible structural 
                    metal must also be bonded, although this is unnecessary in 
                    the cases of metal door architrave's, window frames and so 
                    on, unless these parts are connected to the metal structure 
                    of the building (see 
                    Fig 7.2, page 127, Electrician's Guide), which 
                    in practice is unlikely. These bonding requirements do not 
                    apply to Zone 3 where a prefabricated shower or bath is installed 
                    in a bedroom.  
                  In some cases, safety extra-low voltage (SELV) at 12V a.c. 
                    or 30V ripple-free d.c. is used within bath and shower basin 
                    (for example for hoists used by disabled persons). Such systems 
                    must be protected against direct contact by the use of barriers 
                    or enclosures to IP2X (not accessible by human fingers) or 
                    must have insulation that will withstand a test voltage of 
                    500 V a.c. for 1 min. The safety source supplying such a SELV 
                    system must be situated outside Zones 0, 1 and 2. Protections 
                    by obstacles (3.4.5), 
                    placing out of reach (3.4.5), 
                    or a non-conducting location (5.8.2) 
                    are not allowed in bath or shower rooms.  
                  In every zone, the only wiring permitted is that feeding 
                    equipment in that zone, or where it must pass through that 
                    zone to reach another unless it is buried deeper than 50mm 
                    from the surface. For example, wiring to fixed equipment in 
                    Zone 0 may have to pass through Zones 1, 2 and 3 to reach 
                    its destination. Zone 2 may be used as a route for wiring 
                    needed to feed equipment in Zone 1 below the bath tub or shower 
                    or shower basin. In other words, the zones in a shower or 
                    bathroom must not be used as routes for through wiring that 
                    feeds other services outside the area. 
                   Switch and control gear is permitted in any zone if such 
                    gear is incorporated in the equipment installed there, which 
                    is suitable for use in that zone. No other switch or control 
                    gear is permitted in Zone 0. In Zone 1, only switch and control 
                    gear for SELV may be installed, but the safety source for 
                    the system must be installed outside Zones 0, 1 and 2. In 
                    Zones 2 and 3 or outside the zones but within the bath or 
                    shower room, switches and socket outlets are permitted providing 
                    that they are fed from an SELV source installed outside Zones 
                    0, 1 and 2. The exception to this is the socket outlet on 
                    a shaver supply unit that complies with BS EN 60742, Chapter 
                    2, Section 1, which may be installed in Zones 2 and 3. Insulated 
                    operating cords of pull switches are permitted in Zones 1, 
                    2 and 3 but they must comply with BS 3676. All equipment installed 
                    in Zone 3 must be protected by an RCD with a rating not exceeding 
                    30 mA.  
                  Electrical equipment installed in a room containing a bath 
                    or shower must have protection against the ingress of water 
                    as follows:-  
                   in Zone 0, only equipment which is intended for that 
                    situation, water protected to IPX7 or  
                   in Zones 1 and 2, IPX4 or  
                    which is protection from splashing. Where water jets may be 
                    used for cleaning, such as in public bath and shower facilities, 
                    IPX5 or applies, which gives protection against water jets. 
                   
                  in Zone 3, IPX5 or must again be used if cleaning 
                    by water jets is likely. See (Table 
                    2.4.), for details of the index of protection (IP) system. 
                   
                  Fixed current-using equipment may be installed in Zone 0 
                    if this is the only reasonable location for it and it is suitable 
                    for the conditions in the zone. Water heaters and shower pumps 
                    may be installed in Zones 1 and 2, as may other equipments 
                    suitable for the conditions, provided that they have the required 
                    protection against water and are protected by an RCD with 
                    a rating of not more than 30 mA. In Zone 2, luminaires, fans, 
                    heating appliances and units for whirlpool baths may also 
                    be installed, provided that they comply with the relevant 
                    standards. Electric under-floor heating may be installed provided 
                    that below any zone a metallic grid or plate connected to 
                    the local supplementary equipotential bonding covers it. SELV 
                    equipment may be used in any zone provided that its safety 
                    source is installed outside Zones 0, 1 and 2.  
                  
                  Fig 7.1g) - Zones for a shower room without 
                    a basin and  
                    having a demountable shower head.  
                  Remember this Amendment is optional until 1.1.2002 Now return 
                    to Section 7.3, page 128 of Published by EPA Press Tel 01799 
                    541207 Fax 01799 541166  
                   |