7.2.2A - Bath and shower room requirements (amended)
The revised Regulations for bath and shower rooms are based
on the dimensions of four zones into which the space is divided.
Zone O.
is the interior of the bathtub or the shower basin. In those
cases where a shower has no basin, the zone extends 50mm above
the floor and includes the volume within the vertical surface
at a radius of 1.2m from the water outlet position of a demountable
shower head, or at a radius of 0.6m from the position of a
fixed shower head.
Zone 1.
extends from Zone 0 up to 2.25m above the floor, and outwards
to the extent of the bath or basin, or the extent of Zone
0 as defined above where there is no shower basin. It includes
the space below a bath or shower tub or basin where that space
is accessible without the use of a tool.
Zone 2.
extends outside Zone 1 for 0.6m horizontally and up to a height
of 2.25m. If the ceiling height is more than 2.25m, the space
above Zone 1 up to 3m is also zone 2
Zone 3.
extends outside Zone 2 for 2.4m horizontally and up to a height
of 2.25m. If the ceiling height is more than 2.25m, the space
above Zone 2 up to 3 m is also Zone 3
If the space under a bathtub or shower basin can only be accessed
with the use of a tool, that space is outside the zones. If
no tool is required the space is Zone 1.
The extent of the zones is shown in Figs 7.1b) to 7.1g) in
diagrams which are not to scale.
Figure 7.1b) - Zones for a bathroom (plan).
Note that the same zones apply to a shower room with a shower
basin.
Figure 7.1c) - Zones for a bathroom (elevation).
Note that the same zones apply to a shower room with a shower
basin.
Figure 7.1d) - Zones for a shower with
no basin and a fixed head.
Figure 7.1e) - Zones for a shower room
(elevation)
without a basin and having a fixed showerhead.
Where SELV (safety extra-low voltage, see (3.4.4)
is used, protection against direct contact must be provided
by barriers or enclosures to IP2X (no finger contact) or by
insulation which will withstand 500 V a.c for one minute.
PELV (which is earthed SELV) is not permitted in bath and
shower rooms. Local supplementary equipotential bonding must
be installed to connect together the exposed conductive parts
of Class 1 and Class 11 equipment in Zones 1,2, and 3 together
with extraneous conductive parts, such as metal baths and
shower trays, metallic pipes for water, gas, central heating,
air conditioning. etc in all zones. Accessible structural
metal must also be bonded, although this is unnecessary in
the cases of metal door architrave's, window frames and so
on, unless these parts are connected to the metal structure
of the building (see
Fig 7.2, page 127, Electrician's Guide), which
in practice is unlikely. These bonding requirements do not
apply to Zone 3 where a prefabricated shower or bath is installed
in a bedroom.
In some cases, safety extra-low voltage (SELV) at 12V a.c.
or 30V ripple-free d.c. is used within bath and shower basin
(for example for hoists used by disabled persons). Such systems
must be protected against direct contact by the use of barriers
or enclosures to IP2X (not accessible by human fingers) or
must have insulation that will withstand a test voltage of
500 V a.c. for 1 min. The safety source supplying such a SELV
system must be situated outside Zones 0, 1 and 2. Protections
by obstacles (3.4.5),
placing out of reach (3.4.5),
or a non-conducting location (5.8.2)
are not allowed in bath or shower rooms.
In every zone, the only wiring permitted is that feeding
equipment in that zone, or where it must pass through that
zone to reach another unless it is buried deeper than 50mm
from the surface. For example, wiring to fixed equipment in
Zone 0 may have to pass through Zones 1, 2 and 3 to reach
its destination. Zone 2 may be used as a route for wiring
needed to feed equipment in Zone 1 below the bath tub or shower
or shower basin. In other words, the zones in a shower or
bathroom must not be used as routes for through wiring that
feeds other services outside the area.
Switch and control gear is permitted in any zone if such
gear is incorporated in the equipment installed there, which
is suitable for use in that zone. No other switch or control
gear is permitted in Zone 0. In Zone 1, only switch and control
gear for SELV may be installed, but the safety source for
the system must be installed outside Zones 0, 1 and 2. In
Zones 2 and 3 or outside the zones but within the bath or
shower room, switches and socket outlets are permitted providing
that they are fed from an SELV source installed outside Zones
0, 1 and 2. The exception to this is the socket outlet on
a shaver supply unit that complies with BS EN 60742, Chapter
2, Section 1, which may be installed in Zones 2 and 3. Insulated
operating cords of pull switches are permitted in Zones 1,
2 and 3 but they must comply with BS 3676. All equipment installed
in Zone 3 must be protected by an RCD with a rating not exceeding
30 mA.
Electrical equipment installed in a room containing a bath
or shower must have protection against the ingress of water
as follows:-
in Zone 0, only equipment which is intended for that
situation, water protected to IPX7 or
in Zones 1 and 2, IPX4 or
which is protection from splashing. Where water jets may be
used for cleaning, such as in public bath and shower facilities,
IPX5 or applies, which gives protection against water jets.
in Zone 3, IPX5 or must again be used if cleaning
by water jets is likely. See (Table
2.4.), for details of the index of protection (IP) system.
Fixed current-using equipment may be installed in Zone 0
if this is the only reasonable location for it and it is suitable
for the conditions in the zone. Water heaters and shower pumps
may be installed in Zones 1 and 2, as may other equipments
suitable for the conditions, provided that they have the required
protection against water and are protected by an RCD with
a rating of not more than 30 mA. In Zone 2, luminaires, fans,
heating appliances and units for whirlpool baths may also
be installed, provided that they comply with the relevant
standards. Electric under-floor heating may be installed provided
that below any zone a metallic grid or plate connected to
the local supplementary equipotential bonding covers it. SELV
equipment may be used in any zone provided that its safety
source is installed outside Zones 0, 1 and 2.
Fig 7.1g) - Zones for a shower room without
a basin and
having a demountable shower head.
Remember this Amendment is optional until 1.1.2002 Now return
to Section 7.3, page 128 of Published by EPA Press Tel 01799
541207 Fax 01799 541166
|