7.3.2 - Special requirements for swimming pools
Appliance and sockets for use in these
high-risk areas must be separated extra-low voltage (SELV)
type, at a potential not exceeding 12 V ac or 30 V dc. Such
equipment must be protected to level IP2X, which means that
it must be impossible to touch live parts with a finger,
or must have insulation capable of withstanding a voltage
level of 500 V r.m.s. for one minute. The safety source
(a transformer in most cases), must be installed outside
zones A, B and C. An exception is the supply to floodlights
(often they will be under water) which can be fed at up
to 18 V, if in zones B or C, or 12 V if in zone A (submerged),
each floodlight being powered by a separate transformer
or a separate secondary winding of a transformer having
multiple secondary windings.
Normal luminaires are not permitted in
zones A or B, so general illumination is best provided by
luminaires mounted higher than 2.5 m above floor level.
This is zone C, where protection must be by electrical separation
(see
{5.8.4}) or by 30 mA residual current device(s). If
RCDs are used, care must be taken to ensure that devices
are not tripped by high leakage currents on starting; the
use of multiple circuits, each with its own RCD, is advised.
Attention is drawn to the difficulty of servicing luminaires
mounted above the pool.
Usually, protection against direct contact
will be by means of earthed equipotential bonding and automatic
disconnection of the supply in the event of a fault (the
same as for most other installations), and the special requirements
are:
1. - all extraneous conductive parts,
including non-insulating floors, must be bonded together
and to earth. If the floor within zones B and C is not insulated
or if a PME supply is used (see{5.6})
a metal grid must be installed in the floor and connected
to the local supplementary bonding. The exception to this
is any SELV system, which must remain unconnected to the
main earthing system.
2. - the earth fault loop impedance
must be low enough so as to allow disconnection within 0.4
s (see
{5.3}).
In no case is it permissible to rely for
protection against direct contact on obstacles, placing
out of reach, a non-conducting location or earth-free equipotential
bonding. If wiring is run on the surface it must not be
metallic sheathed and must not he run in metal conduit or
metal trunking, except in zone C.
Enclosures used for wiring systems or appliances
at swimming pools are subject to special requirements, which
depend on whether water jets will be used for cleaning purposes.
If they will be used, protection must be to IPX8, (submersion
in water), within the pool (Zone A) and IPX5, which means
that there must be effective protection against
such water jets (see
{Table 2.1}). If water jets will not be used, protection
depends on the zone (see
{7.3.1}) in which the system or appliance is situated.
The requirements are:
Zone A
IPX8, which means protection from submersion in water,
Zone B
IPX4, so that protection is provided against splashing
water, and
Zone C
indoor pools, IPX2, which gives protection against dripping
water when inclined at 15°; and outdoor pools, 1PX4, which
gives protection against splashing water.
There must be no switchgear, control gear
or accessories installed within zones A or B, except for
small pools where socket outlets are necessary and cannot
possibly be installed outside zone B. In this case, BS 4343
socket outlets may be installed provided they are at least
1.25 m (arms' reach) outside zone A, are at least 0.3 m
above the floor, and are protected by an RCD with a 30 mA
rating or are protected by electrical separation [413-05]
with the necessary isolating transformer situated outside
zones A, B and C. Wiring must not be metallic sheathed,
or enclosed in metallic conduit or trunking if run on the
surface. Joint boxes may be used, but they must be inaccessible
if installed in zones A or B. Instantaneous water heaters
complying with BS 3456 may be installed in zones B and C.
Socket outlets (in zone C only - but see
above for small pools) must be to industrial standard BS
4343, and a shaver outlet to BS EN 60742 may also be installed
in zone C (5.8.4).
If electric floor heating is used around a pool, it must
have its metal sheath, or a covering metal grid if there
is no metallic sheath, connected to the local equipotential
bonding. Fire alarm, audio and public address equipment
should ideally be outside zones A and B, but where this
is not possible must be more than 1.25 metres outside zone
A. Loudspeakers must be out of reach of anyone in the water
or at the poolside, and if portable microphones are used
they must be connected by way of a suitable isolating transformer.
Radio microphones will reduce the danger of shock. Hard
wired telephones are not permitted in any zone, and if required,
cordless telephones must be used with the base unit outside
the zones. Where the basin of a fountain is not intended
to be occupied by people, installations in zones A and B
may be protected by electrical separation (see
{5.8.4}) or by automatic disconnection of the supply
using an RCD with an operating current not exceeding 30
mA.