7.6.2 - Agricultural installations
Of paramount importance where livestock
are present is the indication that the levels of separated
extra-low voltage (SELV) are too high. Whilst the Regulations
do not suggest a safe voltage for animals, simply suggesting
a level 'appropriate to the type of livestock', a practical
value is likely to be no higher than 25 V. Such systems,
as well as those complying with SELV requirements, must
be protected to IP44 (ie, protected from solid objects not
exceeding 1 mm and from splashing water) or the insulation
must be able to withstand 500 V r.m.s. for one minute.
All socket outlets must be protected by
residual current device(s) (RCDs) with an operating current
of no more than 30 mA. Whilst it is accepted that livestock
cannot be protected by earthed equipotential bonding and
automatic disconnection (sometimes known as EEBAD) because
the voltages to which they would he subjected in the event
of a fault are unsafe for them, changes to standard installation
requirements do offer some additional protection. The requirements
are:
1. - Disconnection times for the
operation of protective devices are reduced, usually to
half the normal value. The maximum times are voltage related,
and are shown in {Table 7.3}.
Table 7.3 - Maximum
disconnection times for agricultural circuits for
----------------- livestock (TN systems) |
|
Supply voltage (Uo)
|
Disconnection time
|
|
(volts)
|
(seconds)
|
|
120
|
0.35
|
|
220 to 277
|
0.20
|
|
400 and 480
|
0.05
|
The application of these reduced connection
times leads to the reduced levels of maximum
earth-fault loop impedance, shown in {Table
7.4} for 240
V circuits.
2.
- Fixed equipment and distribution circuits are permitted
to have a disconnection time of 5 s, which is the same as
for normal installations, and require the maximum earth-fault
loop impedance values shown in {Tables
5.2 and
5.4}. An exception is where the fixed equipment is fed
from the same distribution board as circuits requiring disconnection
in 0.2 s at 240 V. In such a case Either the resistance
of the main protective conductor from the distribution board
to the point of connection to the main equipotential bonding
system must be low enough to ensure that its volt drop when
fault current flows does not exceed 25 V,
or the distribution board must have its
exposed conductive parts bonded to all extraneous conductive
parts (such as water pipes) in the area.
3. - The maximum of 25 V for the
potential difference across the protective conductor under
fault conditions stated above is applied to all final circuits.
This is half of the level accepted in other installations,
so the protective conductor resistance must have half the
normal value. Note that where an IT system (usually a generating
plant) is used, special requirements apply - these are outside
the scope of this Guide, and advice must be sought from
a qualified electrical engineer.
4. - Supplementary equipotential
bonding must be applied to connect together all exposed
and extraneous conductive parts which are accessible to
livestock and the main protective system. It is recommended
that a metallic grid should be laid in the floor and connected
to the protective conductor.
5. - Where an RCD is used it is
important to ensure that the earth electrode resistance
is not so high that the 25 V level will be exceeded before
operation. This can be verified by using the expression
where RA = the combined earth
electrode and protective conductor resistance,
and An = the rated residual operating current of the RCD.
Application of the expression gives 833
Ohms for a 30 mA device, 250 Ohms for a 100 mA, 83 ohms
for a 300 mA and 50 Ohms for a 500 mA. Values higher than
200 Ohms should not be used or there may be instability.
The resistance of the protective conductors is usually negligible
compared with that of the earth electrode.
The equipotential bonding required will
create an earth zone, and special measures are necessary
where a circuit fed from this zone extends outside it. If
the equipment could be touched by a person in contact with
the general mass of earth, disconnection time must not exceed
0.2 s, even for fixed equipment. This means that {Table
7.4}
will apply to such circuits.
Fire is a particular hazard in agricultural
premises where there may be large quantities of loose straw
or other flammable material. A particular fire hazard on
agricultural premises is damage to the wiring by rodents
gnawing at cables. This effect can be reduced by cable runs
which are below ceilings rather than in roof spaces and
by the use of steel conduits. The Regulations require the
protection of the system by an RCD with an operating current
not greater than 500 mA. In practice, a 300 mA rating is
likely to be used. This will result in problems of discrimination
between this unit and those of lower operating current rating
unless the main RCD is of the time delayed type (see
{5.9.3}). Care must be taken to ensure that heaters
are not in positions where they will ignite their surroundings;
a clearance of at least 500 mm is required for radiant heaters.
All electrical equipment must be protected
to IP44, and chosen to be suitable to operate under the
onerous conditions they will experience. Wiring must be
inaccessible to livestock and must be vermin proof. In practice,
this will probably mean enclosure in galvanised steel conduit,
or the use of mineral insulated cables, Switch and control
gear must be to IP44 and constructed of, or enclosed in,
insulating material. Switches for emergency use must not
be in positions accessible to cattle, or where cattle may
make operation difficult. Emergency switches should
disconnect all live conductors including the neutral. It
may be necessary to omit isolators in some cases to ensure
that essential supplies (such as broiler house fans) are
not disconnected unintentionally. The likelihood of panic
amongst animals when emergencies occur must be taken into
account.
Table 7.4 - Maximum
earth-fault loop impedance values for 240 V agricultural
circuits to give a maximum 0.2 s disconnection time |
Type of protection |
Protection rating
|
Max. loop impedance
|
|
(A)
|
(ohms)
|
Cart. Fuse, BS 1361 |
5
|
9.60
|
|
15
|
3.00
|
|
20
|
1.55
|
|
30
|
1.00
|
Cart. Fuse BS 88 pt 2 |
6
|
7.74
|
|
10
|
4.71
|
|
16
|
2.53
|
|
20
|
1.60
|
|
25
|
1.33
|
|
32
|
0.92
|
MCB type 1 |
5
|
12.00
|
|
10
|
6.00
|
|
15
|
4.00
|
|
20
|
3.00
|
|
30
|
2.00
|
MCB type 2 |
5
|
6.86
|
|
10
|
3.43
|
|
15
|
2.29
|
|
20
|
1.71
|
|
30
|
1.14
|
MCB type 3 |
5
|
4.80
|
|
10
|
2.40
|
|
15
|
1.60
|
|
20
|
1.20
|
|
30
|
0.80
|