3.8.3 - Protection
omitted
There are cases where a break in circuit
current due to operation of a protective device may cause
more danger than the overload or fault. For example, breaking
the supply to a lifting electromagnet in a scrap yard will
cause it to drop its load suddenly, possibly with dire consequences.
If the field circuit of a dc motor is broken, the reduction
in field flux may lead to a dangerous increase in speed.
A current transformer has many more secondary than primary
turns, so dangerously high voltages will occur~if the secondary
circuit is broken.
In situations like these the installation
of an overload alarm will give warning of the faulty circuit,
which can be switched off for inspection when it is safe
to do so. The possibility of short circuits in such cables
will be reduced if they are given extra protection.
Probably the most usual case of omission
of protection is at the incoming mains position of a small
installation. Here, the supply fuse protects the installation
tails and the consumer's unit. The unprotected equipment
must, however, comply with the requirements for otherwise
unprotected systems listed in {3.7.4}.
|